PURPOSE: To describe the Laboratory standard operating procedure for measurement of Biological Oxygen Demand of Water and Waste Water samples. SCOPE: Applicable to the Laboratory for analysis of Water and Waste Water samples, where measurement of Biological oxygen demand is required.   RESPONSIBILITY:  Lab chemist: Analysis of sample for measurement of Biological Oxygen demand. Technical Manager:   Review of activity  Quality Manager: Implementation and compliance of SOP. PROCEDURE:  Principle: Biochemical Oxygen Demand (BOD) is defined as the amount of O2 required by microorganisms while stabilizing biologically decomposable organic matter in a waste under aerobic conditions. Instrument and Equipment: BOD bottles 300ml capacity, BOD Incubator to be controlled at 27oC ± 1oC. Reagents:  Phosphate buffer: Dissolve 8.5 g KH2PO4, 21.75 g K2HPO4, 33.4 g Na2HPO4.7H2O and 1.7 g NH4Cl in distilled water and dilute to 1000ml. Adjust its pH to 7.2. Magnesi...
Welcome to our comprehensive blog on Testing Method SOP (Standard Operating Procedures)! Here, we delve into essential methodologies for creating, implementing, and optimizing standard operating procedures in various testing environments. Whether you're involved in environmental testing, laboratory assessments, or quality control, our insights will guide you through best practices and innovative strategies. Discover how to enhance efficiency